Code Compliance Verification
443-945-1289
Code Requirements
Every state that adopts the International Energy Conservation Code may have amendments. Learn more about your state's specific code requirements below.
Maryland
Envelope leakage: <= 3.00 ACH50
Duct leakage: <= 4.0% Qn*
​
Total duct leakage testing is required regardless if ductwork is in 100% conditioned space.
​
* Qn = tested CFM25 divided by area served
Delaware
Envelope leakage: <= 3.00* ACH50
Duct leakage: <= 6.0% Qn**
​
* buildings 1,500 SF or less: <= 5.00 ACH50
* buildings 1,501-2,000 SF: <= 4.00 ACH50
* buildings 2,000+ SF: <= 3.00 ACH50
** Qn = tested CFM25 divided by area served
Virginia
Blower door testing is required in select jurisdictions with a maximum ACH50 or 5.00